CHINT NXU-II Surge Protection Device (SPD): Type 2 surge arrester that diverts lightning and switching surges away from your equipment. Available in 40kA and 65kA ratings.

Technical specifications

  • Type: Type 2 / Class II SPD (IEC 61643-11)
  • Max continuous voltage (Uc): 275V AC (single-phase 230V, L-N) or 385V AC (three-phase 400V / TT system). Listed part numbers above are 385V; 275V on request
  • Max discharge current (Imax): 40kA or 65kA (8/20µs)
  • Nominal discharge current (In): 20kA (40kA model) / 30kA (65kA model)
  • Voltage protection level (Up): ≤1.5kV (40kA/275V), ≤1.8kV (40kA/385V), ≤2.2kV (65kA/385V)
  • Response time: ≤25ns
  • Frequency: 50/60Hz
  • Poles: 1P, 2P, 4P (select above)
  • Status indicator: green = normal, red = replace module
  • Mounting: 35mm DIN rail, plug-in replaceable module

Genuine CHINT stock, nationwide delivery from Magnet Engineering.

+ −
  • CHINT NXU-II Surge Protection Device (SPD), 385V

    ৳ 6,810.00

    Request a Call Back

    •  Ask a Question

      CHINT NXU-II Surge Protection Device (SPD), 385V

      ৳ 6,810.00

      Ask a Question

        ... people are viewing this right now

        Share
      Guaranteed Safe Checkout

      Description

      The CHINT NXU SPD is a surge protection device that diverts lightning and switching surges away from your equipment. This listing covers the CHINT NXU-II Surge Protection Device (SPD), 385V. Check the latest CHINT NXU SPD price in Bangladesh on this page and order genuine stock from Magnet Engineering.

      CHINT NXU SPD specifications

      Brand CHINT
      Product CHINT NXU-II Surge Protection Device (SPD), 385V
      Series NXU-II / NXU-IIG
      Max continuous voltage (Uc) 275V AC or 385V AC (part numbers listed below are 385V)
      Max discharge current 40 kA / 65 kA
      Type Surge Protection Devices (SPD)
      Options available 5 rating options
      Price MRP shown above (CHINT Bangladesh list, October 2026)

      Available ratings and part numbers

      Select the option you need from the menu above. The table below shows the CHINT model / part number and MRP for each option, so you can match it to your drawing or BOQ.

      Rating Model / part number MRP (BDT)
      40kA 2P (Type 2, 18mm module) G NXU-II 40kA/385V 2P 18mm(R) 1,940
      40kA 4P (Type 2, 36mm) G NXU-II 40kA/385V 4P 36mm(R) 4,030
      65kA 1P (Type 2, high capacity) G NXU-IIG 65kA/385V 1P 2,830
      65kA 2P (Type 2, high capacity) G NXU-IIG 65kA/385V 2P 5,620
      65kA 4P (Type 2, high capacity) G NXU-IIG 65kA/385V 4P 11,250

      Technical specifications: 40kA vs 65kA

      275V or 385V? Use Uc 275V for single-phase 230V supply (L-N) in TN systems. Use Uc 385V for three-phase 400V boards, TT systems, or where the supply voltage runs high. The part numbers in our list above are 385V; 275V versions are available on request.

      Parameter NXU-II 40kA/385V NXU-IIG 65kA/385V
      SPD type Type 2 / Class II Type 2 / Class II (high capacity)
      Max continuous operating voltage (Uc) 275V AC / 385V AC 385V AC
      Nominal discharge current In (8/20µs) 20kA 30kA
      Max discharge current Imax (8/20µs) 40kA 65kA
      Voltage protection level (Up) ≤1.5kV (275V) / ≤1.8kV (385V) ≤2.2kV
      Response time ≤25ns ≤25ns
      Rated frequency 50/60Hz 50/60Hz
      Poles available here 2P, 4P 1P, 2P, 4P
      Fault indication Window: green normal, red failed Window: green normal, red failed
      Mounting 35mm DIN rail, plug-in module 35mm DIN rail, plug-in module
      Standard IEC 61643-11 / GB/T 18802.1 IEC 61643-11 / GB/T 18802.1

      n

      Where it is used

      Install it at the main distribution board or sub-boards of homes, offices, factories, telecom sites and solar systems to protect electronics, drives and controllers. See all items in our Surge Protection Devices (SPD) range.

      How to choose the right one

      Use 40 kA for normal distribution boards and 65 kA for main boards in exposed or lightning-prone sites. Use 2P (or 1P+N) for single-phase and 4P (or 3P+N) for three-phase supply; pick 275V for single-phase 230V and 385V for three-phase 400V. Always fit a suitable MCB or fuse in front of the SPD.

      Why buy from Magnet Engineering

      Since 2018, Magnet Engineering has supplied electrical and mechanical items to the power sector and industry in Bangladesh. Every CHINT item we sell is original stock. We offer nationwide delivery, cash on delivery and project pricing on request. Call +8801716603115.

      Based on 0 reviews

      0.00 Overall
      0%
      0%
      0%
      0%
      0%
      Be the first to review “CHINT NXU-II Surge Protection Device (SPD), 385V”

      Your email address will not be published. Required fields are marked *

      Reviews

      There are no reviews yet.

      SKU: 1791974121-8 Category:
      Close
      Close My Cart
      Close Wishlist
      Recently Viewed Close
      Close

      Close
      Navigation
      Categories